Specifications
Table 19. Technical SpecificationsTechnology | Online, |
| optional |
| Frequency independent operation. |
Input Voltage Range | |
Input Isolation | 208V or 240V ±20% |
Transformer Input |
|
Voltage Range |
|
Input Power Factor | >0.99 at full load nominal line conditions |
Input Rated Voltage | 100/200, 110/220, or 120/240 Vac with 180° phase displacement |
| 120/208 or 127/220 Vac with 120° phase displacement |
Input Frequency Range | |
Input Rated Frequency | |
Output Voltage | ±1% static, Phase to Neutral |
Regulation | ±2% static, Phase to Phase |
| ±5% dynamic at 100% resistive load change |
| Response time <1 ms |
Output Voltage | <2% THD linear load |
Distortion | <5% THD |
Output Frequency | |
Output Frequency | Synchronization to line |
Regulation |
|
Output Frequency | |
Conversion | Frequency Conversion mode can be configured through the front panel or |
| through XCP commands. |
| Bypass is not available in Frequency Conversion mode. |
Output Overload | |
| |
| |
| >150% for 300 milliseconds |
Powerware® 9155 UPS | 87 |