Specifications

Table 19. Technical Specifications

Technology

Online, double-conversion, split-phase topology with Static Bypass switch and

 

optional 3-position Maintenance Bypass switch.

 

Frequency independent operation.

Input Voltage Range

75–144 Vac per phase

Input Isolation

208V or 240V ±20%

Transformer Input

 

Voltage Range

 

Input Power Factor

>0.99 at full load nominal line conditions

Input Rated Voltage

100/200, 110/220, or 120/240 Vac with 180° phase displacement

 

120/208 or 127/220 Vac with 120° phase displacement

Input Frequency Range

45–65 Hz

Input Rated Frequency

50/60-Hz selectable, auto-configuring

Output Voltage

±1% static, Phase to Neutral

Regulation

±2% static, Phase to Phase

 

±5% dynamic at 100% resistive load change

 

Response time <1 ms

Output Voltage

<2% THD linear load

Distortion

<5% THD non-linear load

Output Frequency

50/60-Hz selectable or auto-configuring

Output Frequency

Synchronization to line

Regulation

 

Output Frequency

Frequency/phase-converter operation with derated output load capacity to 80%;

Conversion

Frequency Conversion mode can be configured through the front panel or

 

through XCP commands.

 

Bypass is not available in Frequency Conversion mode.

Output Overload

101–110% for 10 minutes

 

111–125% for 60 seconds

 

126–149% for 5 seconds

 

>150% for 300 milliseconds