Operation

User Settings

The following table displays the options that can be changed by the user.

NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect.

Table 13. User Settings

Description

Available Settings

Default Setting

Set Date and Time

Set Month

01/01/2003

 

Date: mm/dd/yyyy

 

Time: 24:00

00:00

 

 

 

Display Contrast

Adjust contrast with up/down

Moderate

 

arrow buttons

 

Change Language

Select Language:

English

 

<English> or <Spanish>

 

 

 

 

Relay Config

Relay: [Alarm 1] [X-Slot 1-1/2/3/4]

Alarm 1: UPS ok

 

or [X-Slot 2-1/2/3/4]

X-Slots (1 or 2)

 

Setup: [Battery Low] [On Battery]

#1: On Battery

 

[On Bypass] [UPS ok] [custom]

#2: Battery Low

 

[empty]

#3: UPS ok

 

 

#4: On Bypass

 

 

 

Signal Inputs

[empty] [Logic]

Empty

 

(see “Programmable Signal Inputs”

 

 

on page 63)

 

Serial Port Config

Port: [X-Slot-1] [X-Slot-2/Serv]

19200

 

Speed: [19200] [9600] [2400]

 

 

[1200]

 

 

 

 

Parallel Operation Settings

Refer to the Powerware 9155

 

 

Parallel UPS (8–15 kVA) User’s

 

 

Guide.

 

Start Screen

Eaton Powerware logo

Eaton Powerware logo

 

Mimic Screen

 

 

 

 

User Password

Enabled/Disabled

Disabled

 

If Enabled is selected, the

 

 

password is USER.

 

 

 

 

Audible Alarms

Normal Sound/Disabled

Normal Sound

 

 

 

Battery Charging

ABM cycling/constant

ABM cycling

 

 

 

68

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com