Operation
User Settings
The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect.
Table 13. User Settings
Description | Available Settings | Default Setting |
Set Date and Time | Set Month | 01/01/2003 |
| Date: mm/dd/yyyy | |
| Time: 24:00 | 00:00 |
|
|
|
Display Contrast | Adjust contrast with up/down | Moderate |
| arrow buttons |
|
Change Language | Select Language: | English |
| <English> or <Spanish> |
|
|
|
|
Relay Config | Relay: [Alarm 1] | Alarm 1: UPS ok |
| or | |
| Setup: [Battery Low] [On Battery] | #1: On Battery |
| [On Bypass] [UPS ok] [custom] | #2: Battery Low |
| [empty] | #3: UPS ok |
|
| #4: On Bypass |
|
|
|
Signal Inputs | [empty] [Logic] | Empty |
| (see “Programmable Signal Inputs” |
|
| on page 63) |
|
Serial Port Config | Port: | 19200 |
| Speed: [19200] [9600] [2400] |
|
| [1200] |
|
|
|
|
Parallel Operation Settings | Refer to the Powerware 9155 |
|
| Parallel UPS |
|
| Guide. |
|
Start Screen | Eaton Powerware logo | Eaton Powerware logo |
| Mimic Screen |
|
|
|
|
User Password | Enabled/Disabled | Disabled |
| If Enabled is selected, the |
|
| password is USER. |
|
|
|
|
Audible Alarms | Normal Sound/Disabled | Normal Sound |
|
|
|
Battery Charging | ABM cycling/constant | ABM cycling |
|
|
|
68 | Powerware® 9155 UPS |