Operation
Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
1.Press any button on the front panel display to activate the menu options.2.Using the
button, scroll to the Settings menu.3.Press the
button twice to select the User Settings menu.4.Using the
button, scroll to the Number of Battery Strings option and press the
button.
5.Use the
or
arrow buttons to select the number of strings according to your UPS configuration:
All | Number of Strings |
| |
UPS + 1 | EBM | 6 |
|
|
|
|
|
UPS + 2 | EBMs | 10 |
|
|
|
|
|
UPS + 3 | EBMs | 14 |
|
|
|
|
|
UPS + 4 | EBMs | 18 |
|
All | Number of Strings |
| |
UPS + 1 | EBM | 10 |
|
|
|
|
|
UPS + 2 | EBMs | 16 |
|
|
|
|
|
UPS + 3 | EBMs | 22 |
|

button to save the setting.7.Press the ESC button until the Eaton Powerware logo appears.Powerware® 9155 UPS | 75 |