Extended Battery Module Installation
7.If additional EBMs are installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
8.Attach a stabilizing bracket to each EBM if needed (see “Stabilizing the Cabinet” on page 49).
9.Continue to one of the following sections:“Communication” on page 53 to install UPS communication options, such as
“Operation” on page 65 to start up the UPS.
NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 75).
|
| ON |
EBM Battery |
|
|
Circuit Breaker | UPS Battery |
|
EBM Cable | OFF | |
| Connector | |
|
| |
EBM Battery Connector |
|
|
UPS Battery
Circuit Breaker
Ground
Strap
Figure 31. Typical EBM Installation
52 | Powerware® 9155 UPS |