Input Isolation Transformer Installation

NOTE Input neutral is supplied by the input isolation transformer.

Table 4. Input Isolation Transformer Terminal Block Wiring

Wire Function

Terminal Position

Minimum Wire Size*

Tightening Torque

 

Input

L1

TB1-1

2 AWG

 

 

 

 

 

 

25 lb in

 

L2 (208V)

TB1-2

2 AWG

 

(2.83 Nm)

 

 

 

 

 

L2 (240V)

TB1-3

2 AWG

 

 

 

 

 

 

 

 

 

Output

L1

TB1-4

3 AWG

 

 

 

 

 

 

25 lb in

 

L2

TB1-5

3 AWG

 

(2.83 Nm)

 

 

 

 

 

Neutral

TB1-6

3 AWG

 

 

 

 

 

 

 

 

Ground

Output

TB1-7

8 AWG

25 lb in

Ground

Input

TB1-8

8 AWG

(2.83 Nm)

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

12.Wire the output of the input isolation transformer terminal block to the UPS input terminal block (see Table 5 and Figure 10).

Table 5. UPS Terminal Block Wiring

Wire Function

Terminal

Minimum

Tightening

Conduit Connection

 

Position

Wire Size*

Torque

(Entry Size)

 

 

 

 

Input

Ground

TB1-1

8 AWG

 

 

 

 

 

 

 

 

 

 

 

L1

TB1-3

3 AWG

25 lb in

2” access hole for

 

 

 

 

 

Neutral

TB1-4

3 AWG

(2.83 Nm)

1-1/2” conduit

 

 

 

 

 

 

 

 

L2

TB1-5

3 AWG

 

 

 

 

 

 

 

 

 

 

Output

L1

TB1-6

3 AWG

 

 

 

 

 

 

 

 

 

 

 

Neutral

TB1-7

3 AWG

25 lb in

2” access hole for

 

 

 

 

 

L2

TB1-8

3 AWG

(2.83 Nm)

1-1/2” conduit

 

 

 

 

 

 

 

 

Ground

TB1-9

8 AWG

 

 

 

*Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

25