
Output overcurrent protection and disconnect switch must be provided by others.
Figure 20 and Figure 21 beginning on page 37 show the oneline diagrams of the MBM and PDM with the UPS.
W A R N I N G
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Use the following procedure to hardwire the MBM/PDM:1.Verify that the electrical connections to the installation site have been properly installed.
2.A
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
Table 6. Circuit Breaker RatingsUPS Capacity | Input Circuit Breaker Rating | Minimum Wire Size* |
|
8 kVA | 60A | 4 AWG (21.2 mm2) | |
10 kVA | 80A | 3 AWG (26.7 mm2) | |
12 kVA | 100A | 2 AWG (33.6 mm2) | |
15 kVA | 100A | 2 AWG (33.6 mm2) |
*Use only
NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Powerware 9155 UPS contain wiring to support the maximum capacity of the UPS cabinet.
3.Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
Powerware® 9155 UPS | 33 |