Operation

Table 13. User Settings (continued)

Description

Available Settings

Default Setting

 

Automatic Battery Tests

Enabled/Disabled

Enabled

 

 

Enabled automatically runs the

 

 

 

battery test once a month.

 

 

 

 

 

 

Number of Battery Strings

0 through 22

2 strings for UPS-32 models

 

 

(see “Configuring the UPS for

4 strings for UPS-64 models

 

 

EBMs” on page 75)

 

 

Battery Capacity

1 through 65535 watts per cell

34 W/cell

 

 

 

 

 

Battery Low Alarm Level

1.750 through 1.950 volts per cell

1.880 V/cell

 

 

 

 

 

Set Nominal Output Voltage

120V/240V

120V/208V

 

 

120V/208V

 

 

 

110V/220V

 

 

 

100V/200V

 

 

 

127V/220V

 

 

 

 

 

 

Bypass Voltage High Limit

+1 through +20% (1% increments)

120V +10%

 

 

 

 

 

Bypass Voltage Low Limit

-1 through -20% (1% increments)

120V -15%

 

 

 

 

 

Nominal Output Frequency

50 Hz or 60 Hz

60 Hz

 

 

 

 

 

Synchronization

Enabled/Disabled

Enabled

 

 

 

 

 

Synchronization Window

±0.5 through ±3.0 Hz

±2.0 Hz

 

 

(0.1 Hz increments)

 

 

 

 

 

 

Unsynchronized Transfer to Bypass

Allowed/Not Allowed

Not Allowed

 

 

 

 

 

Usage of Bypass

Enabled/Disabled

Enabled

 

 

 

 

 

Transfer to Bypass When Overload

After a delay/Immediately

After a delay

 

 

 

 

 

Automatic Start Delay

-1 through 32767 seconds

0s

 

 

(-1 means disabled)

 

 

Automatic On Battery Shutdown

-1 through 32767 seconds

-1s

 

Delay

(-1 means disabled)

 

 

 

 

 

 

Control Commands from X-Slot1

Allowed/Disabled

Allowed

 

 

 

 

 

Control Commands from

Allowed/Disabled

Allowed

 

X-Slot2/Serv

 

 

 

X-Slot Signal Input Activation

0 through 65 seconds

5s

 

Delay

 

 

 

Input signal delayed shutdown

1 through 65535 seconds

120s

 

delay

 

 

 

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

69