Operation
Table 13. User Settings (continued)Description | Available Settings | Default Setting |
|
Automatic Battery Tests | Enabled/Disabled | Enabled |
|
| Enabled automatically runs the |
|
|
| battery test once a month. |
|
|
|
|
|
|
Number of Battery Strings | 0 through 22 | 2 strings for |
|
| (see “Configuring the UPS for | 4 strings for |
|
| EBMs” on page 75) |
|
|
Battery Capacity | 1 through 65535 watts per cell | 34 W/cell |
|
|
|
|
|
Battery Low Alarm Level | 1.750 through 1.950 volts per cell | 1.880 V/cell |
|
|
|
|
|
Set Nominal Output Voltage | 120V/240V | 120V/208V |
|
| 120V/208V |
|
|
| 110V/220V |
|
|
| 100V/200V |
|
|
| 127V/220V |
|
|
|
|
|
|
Bypass Voltage High Limit | +1 through +20% (1% increments) | 120V +10% |
|
|
|
|
|
Bypass Voltage Low Limit | 120V |
| |
|
|
|
|
Nominal Output Frequency | 50 Hz or 60 Hz | 60 Hz |
|
|
|
|
|
Synchronization | Enabled/Disabled | Enabled |
|
|
|
|
|
Synchronization Window | ±0.5 through ±3.0 Hz | ±2.0 Hz |
|
| (0.1 Hz increments) |
|
|
|
|
|
|
Unsynchronized Transfer to Bypass | Allowed/Not Allowed | Not Allowed |
|
|
|
|
|
Usage of Bypass | Enabled/Disabled | Enabled |
|
|
|
|
|
Transfer to Bypass When Overload | After a delay/Immediately | After a delay |
|
|
|
|
|
Automatic Start Delay | 0s |
| |
|
|
| |
Automatic On Battery Shutdown |
| ||
Delay |
|
| |
|
|
|
|
Control Commands from | Allowed/Disabled | Allowed |
|
|
|
|
|
Control Commands from | Allowed/Disabled | Allowed |
|
|
|
| |
0 through 65 seconds | 5s |
| |
Delay |
|
|
|
Input signal delayed shutdown | 1 through 65535 seconds | 120s |
|
delay |
|
|
|
Powerware® 9155 UPS | 69 |