UPS Maintenance

Using the Wall-Mounted Bypass Switch

The wall-mounted bypass switch is rated at 80A/300 Vac and has four positions as described in Table 15.

NOTE In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS.

Table 15. Wall-Mounted Bypass Switch Positions

Switch Position

 

 

 

 

 

 

Description

UPS

Connects the UPS output to the load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE

Connects the load directly to AC input power and disconnects UPS output. AC input

 

power is still connected to the UPS input.

SERVICE

Like the LINE position, SERVICE connects the load directly to AC input power and

 

disconnects UPS output. However, because SERVICE also disconnects AC input

 

from the UPS, this is the appropriate position for UPS maintenance or repair.

OFF

Disconnects the load from the UPS output power and AC input power, as well as AC

 

input power to the UPS input.

 

You must press the red button beside the switch before turning the

 

Maintenance Bypass switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 43. Wall-Mounted Maintenance Bypass Switch

82

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com