UPS Maintenance
Using the Wall-Mounted Bypass Switch
The
NOTE In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS.
Table 15.Switch Position |
|
|
|
|
|
| Description | ||||||
UPS | Connects the UPS output to the load. | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LINE | Connects the load directly to AC input power and disconnects UPS output. AC input | ||||||||||||
| power is still connected to the UPS input. | ||||||||||||
SERVICE | Like the LINE position, SERVICE connects the load directly to AC input power and | ||||||||||||
| disconnects UPS output. However, because SERVICE also disconnects AC input | ||||||||||||
| from the UPS, this is the appropriate position for UPS maintenance or repair. | ||||||||||||
OFF | Disconnects the load from the UPS output power and AC input power, as well as AC | ||||||||||||
| input power to the UPS input. | ||||||||||||
| You must press the red button beside the switch before turning the | ||||||||||||
| Maintenance Bypass switch. | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|