7.Install the conduit to the bypass switch cabinet. AC input and AC output conductors must be run through separate conduit. UPS output circuits must be installed in a dedicated conduit system and not shared with other electrical circuits.
8.Hardwire the terminal strip inside the bypass switch cabinet. Use copper wire that is the appropriate size for the current draw.
See Figure 25 for a detailed view of the terminal strip label.
Figure 25.