Communication

Table 11. Programmable Signal Inputs

Signal

Description

 

Disable Bypass Operation

If active, the automatic transfer to the static bypass is prevented.

 

 

Charger Off

If active, the battery charge function is disabled. In a utility power

 

outage, the discharge of batteries is supported.

Remote ON/OFF

If active, the UPS output turns off regardless of the mode of operation.

 

Auxiliary power, fan, communication, and rectifier/battery charger

 

remain functional. Restart is initiated immediately when this signal is

 

inactive.

 

 

Request Bypass

If active, the UPS transfers to bypass if the bypass voltage, frequency,

 

and synchronization are all okay.

Request Normal

If active, the UPS transfers to inverter operation if not prohibited by

 

REPO or an alarm condition.

Force Bypass

If active, the UPS is forced to static bypass operation regardless of the

 

bypass status.

External Battery Breaker Status

If active, the UPS knows that the batteries are disconnected.

 

 

Building Alarm 1–6

These alarms can be activated separately or at the same time with

 

other building alarms.

Not in Use

Default

 

 

Shutdown

If active, the UPS shuts down immediately.

 

 

Delayed Shutdown

If active, the UPS shuts down after a user-configured delay time.

 

Default shutdown delay is 120 seconds. The UPS automatically restarts

 

when the signal changes to inactive.

 

 

Normal/Bypass

If active, the UPS transfers to bypass if okay. If inactive, the UPS

 

transfers to the inverter when possible.

On Generator

If active, the UPS knows that input is fed from the generator. Bypass is

 

disabled; the automatic battery test is disabled.

External Transformer

This option is not used.

Overtemperature

 

 

64

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com