17. FAULT CODES

When the boiler detects a temporary fault condition, the appropriate code is shown flashing on the display. If/when the fault code is final, the pump will perform a 60-second post circulation and the red LED will be illuminated.

CODE

CAUSE

ALARM TYPE

ACTION

AL10

Ignition failure/not flame sensed,

Final

Reset, check appliance operation

 

condense sensor activated

 

 

AL20

Limit thermostat fault, blocked flue switch,

 

 

 

flue thermostat

Final

Reset, check appliance operation

 

 

 

 

AL21

External device fault (UHT/CPA)

Final

Reset, check appliance

 

 

 

 

AL26

Return temperature too high

Final

Reset, check pump, ensure there is sufficient

 

 

 

flow sensor temperature). Circulation around

 

 

 

heating circuit/s

 

 

 

 

AL28

Temperature differential inverted

Final

Reset, check pump, ensure there is sufficient

 

(return sensor temperature higher than

 

circulation around heating circuit/s thermistors

 

flowsensor temperature)

 

 

 

 

 

 

AL29

Flue sensor over temperature lock out

Final

Reset check appliance operation

 

 

 

 

AL34

Fan blower signal fault

Final

Reset check appliance operation, check fan

 

 

 

 

AL40

Insufficient system water pressure

Final

Check/refill system pressure, reset, check

 

 

appliance operation

 

 

 

 

 

AL41

Insufficient system water pressure

Temporary

Check/refill system pressure, check appliance

 

 

 

operation

 

 

 

 

AL52

Internal fault

Final

Reset, check boiler operation

 

 

 

 

AL55

Jumper tag fault

Final

Check jumper tag configuration

 

 

 

 

AL60

Jumper tag fault

Temporary

Check jumper tag configuration

 

 

 

 

AL71

Primary (flow) sensor fault

Temporary

Check primary thermistor, check wiring

 

 

 

 

AL73

Return sensor fault

Temporary

Check return thermistor, check /wiring

 

 

 

 

AL74

Variation on temperature of primary

Final

Reset, check boiler operation, check

 

 

 

and/or return too high pump, ensure there is

 

 

 

sufficient circulation around heating circuit/s

 

 

 

 

AL79

Flow temperature too high, or

Final

Reset, check appliance operation, check

 

temperature differential between

 

thermistors

 

primary and return too high

 

 

AL91

The main heat exchanger need to be

Advice

Call the Raypak technical service

 

cleaned

 

 

 

 

 

 