2. PLACING THE WALL-MOUNTED XPAK BOILER

XPak boilers are wall mounted. Use only the XPak boiler wall mounting instructions included in the box.

WARNING: The wall must be capable of carrying the weight of the boiler and its related components. The weights of the boiler are approximately:

XPak 85 = 82 lbs (37 kg). XPak 120 = 93 lbs (42 kg).

Failure to comply with above could result in severe personal injury, death or substantial property damage

3. XPAK WALL MOUNTING INSTRUCTIONS

WARNING: This boiler is heavy and awkward to lift. It is recommended and safer to install the boiler with two people. Use caution as to not drop the boiler which could cause personal injury. Verify that the boiler is securely mounted before leaving the boiler unsupervised.

The wall must be vertically plumb and capable of carrying the weight of the XPak and its related components.

The building frame (studs) must be 16" on center. If not, you must use 1/2" minimum plywood 24" x 48", fastened with at least (14) #12 x 3" (3/16" x 3") round head tapping screws to the frame of the building to provide proper support for the boiler. Alternate methods of mounting must not be used. (ex. toggle bolts, hollow wall anchors) or any other fastener other than #12 x 3" (3/16" x 3") round head tapping screws.

CAUTION: If the XPak is not vertically plumb, improper and unsatisfactory operation may occur. This will cause excessive condensation build-up causing unnecessary maintenance and nuisance fault codes.

4. INSTALLATION STEPS

Prior to lifting the XPak Boiler onto the wall, use the enclosed template to level and locate the wall bracket. Mount the wall bracket using lag screws. Ensure the bracket is level when mounted. Extreme care is needed to ensure the bolts are secured in the studs. Hang the boiler on the bracket and secure the bottom of the boiler with two (2) additional lag screws. This will provide additional strength and support to the XPak boiler.

XPAK PIPING

1. RELIEF VALVE

The XPak has a pressure relief valve factory fitted.

Connect discharge piping to safe disposal location, following guidelines in the WARNING below:

WARNING: To avoid water damage or scalding due to relief valve operation:

-Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the discharge line in a manner that will prevent possibility of severe burns or property damage should the valve discharge.

-Discharge line must be as short as possible and be the same size as the valve discharge connection throughout its entire length.

-Discharge line must pitch downward from the valve and terminate no more than 6” (150 mm) above the floor drain where any discharge will be clearly visible.

The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375 °F (190°C) or greater.

-Do not pipe the discharge to any place where freezing could occur.

-Do not plug or place any obstruction in the discharge line.

-Test the operation of the valve after filling and pressurizing system by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.

-For boilers installed with only a pressure relief valve, the separate storage vessel must have a temperature and pressure relief valve installed. This relief valve shall comply with the standard for Relief Valves for Hot Water Supply Systems, ANSI Z21.22/CSA4.4.

-Failure to comply with the above guidelines could result in failure of the relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.

2. GENERAL PIPING INFORMATION

CAUTION: Use two wrenches when tightening water piping at boiler, using one wrench to prevent the boiler return line or supply line from turning. Failure to support the boiler piping connections to prevent them from turning could cause damage to boiler components.

NOTICE: The XPak boiler control module uses temperature sensors to provide both high limit protection and modulating temperature control. The PCB also provides low water protection using a water pressure switch (minimum 6.5 psi (0.45 bar)) and blocked flue switch. Some codes/jurisdictions may require additional external controls for high limit and/or low water cutoff protection.

3. SEPARATE LOW WATER CUTOFF

A low water cutoff may be required by state local code or some insurance companies. Check code requirements before installation of the XPak boiler.

If required:

-Use a low water cutoff designed for hydronic installations

-Follow low water cutoff manufacturer’s instructions

NOTICE:

A hot water boiler installed above radiation level or as required by the Authority having jurisdiction, must be provided with a low water cut off device either as apart of the boiler or at the time of the boiler installation.

4. BACKFLOW PREVENTER

Use a backflow preventer specifically designed for hydronic boiler installations. This valve should be installed on the cold water fill supply line per local codes.

5.FITTING THE HEATING CIRCUIT SUPPLY AND RETURN PIPES

NOTICE:

-To protect the entire heating system Raypak recommends installing a filter in the return circuit. When connecting the boiler to an existing heating system this filter must definitely be installed.

-Install shut-off valves immediately before and after the dirt particle filter to enable the filter to be cleaned.

-Install a filling and drain cock in the heating system supply pipe if required.

-Also install a safety valve in the system.

NOTICE: When using oxygen-permeable pipes, e. g. for floor heating systems, you must separate the system using heat exchangers.

-Thoroughly flush all pipes and radiators.

-Refer to the installation template for the pipe connection dimensions.

-Connect the pipes so that they are free from strain.

6.EXPANSION TANK AND MAKE-UP WATER

1.Ensure expansion tank size will handle boiler and system water volume and temperature. Allow 2 gallons for the boiler and its piping.

CAUTION: Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual failure can result due to excessive make-up water addition.

2.Expansion tank must be located near to the boiler as shown in Piping “XPak installation diagrams”. No valve is to be placed between the boiler and the expansion tank.

7. SIZING SPACE HEAT SYSTEM PIPING

-Size the piping and components in the space heating system using recognized design methods.

NOTICE:

-The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler and with appropriate valves to prevent the chilled medium from entering the boiler.

-The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.

17

Page 17
Image 17
Raypak 120, 85 manual Xpak Piping

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.