CONDENSATE TRAP REMOVAL (Fig. 79)
Disconnect the 2 upper rubber condensate pipes (A). Remove the pin (B) that secures the trap to the air box plate. Disconnect the lower rubber condensate pipe (C) from the condensate trap. Carefully remove the condensate trap. Replace in the reverse order.
FLUE COLLECTOR AND FLUE THERMOSTAT REMOVAL (Fig. 80)
Unclip and remove the air chamber front and left side covers. Locate and remove the screw (A) that secures the flue gas analysis test point cover (B). Disconnect the silicon pipe (right hand) of the blocked flue switch. Remove the clip (C) and the flue thermostat (D). Gently pull down and to the left and ease the flue collector from its location. Replace in the reverse order.
A |
|
| B |
| C |
| A |
| B |
| C |
Fig. 79 |
|
| B |
| A |
D | C |
|
Fig. 80
55