Raypak 120, 85 manual FAN SPEED rpm TABLE, Model, 5,800, 2,000, 3,700, 5,600, 1,500

Models: 120 85

1 68
Download 68 pages 52 Kb
Page 47
Image 47
FAN SPEED (rpm) TABLE

NOTICE: When the request for heating and/or hot water has been satisfied, the boiler pump and fan may continue to circulate to dissipate any residual heat within the boiler.

7. BOILER FAN SPEEDS

The boiler fan speeds require to be checked and/or adjusted prior to making any adjustments to the gas valve or if the main PCB has been replaced.

ATTENTION

Gas type and appliance fan speed (output) must be set according to the specific appliance specification. Raypak accepts no responsibility if the gas type and/or fan speed is not correctly adjusted according to the respective appliance specification as detailed on the appliance data badge.

CHECKING/ADJUSTING THE BOILER FAN SPEEDS

Move the selector switch to the OFF position and remove the 3- selector knobs.

ABSOLUTE MAX FAN SPEED

Locate the MAX trim pot (Fig. 59) and gently adjust clockwise or counterclockwise to achieve the correct fan speed (see Table 10 below). NOTICE: The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

ABSOLUTE MIN FAN SPEED

Locate the MIN trim pot (Fig. 59) and gently adjust clockwise or counterclockwise to achieve the correct fan speed (seeTable 10 below).

NOTICE: The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

IGNITION FAN SPEED

NOTICE: Do this operation only after the adjusting of absolute max and min fan speed.

LocatetheIGNtrimpot (Fig. 59) andgentlyadjustclockwiseorcounter clockwise to achieve the correct fan speed (see Table 10 below).

NOTICE: The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

HEATING FAN SPEED

Locate the HTG trim pot (Fig. 59) and gently adjust clockwise or counter clockwise to achieve the correct fan speed (see Table 10 below).

NOTICE: The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

FAN SPEED TABLE

Use the following table to set the corresponding fan speeds that are relative to the boiler you are working on.

 

FAN SPEED (rpm) TABLE

 

Tab. 10

 

 

MODEL

MAX

MIN

HTG

IGN

 

 

85

5,800

2,000

5,800

3,700

 

 

120

5,600

1,500

5,600

3,700

 

 

 

 

 

 

 

 

 

HTG

 

 

CO

IGN

 

 

 

TMR

MIN

MAX

 

 

Fig. 59

A

B

Fig. 59a

8.CHECKING THE CO2 AND ADJUSTING THE GAS VALVE THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE AID OF A PROPERLY CALIBRATED FLUE GAS ANALYZER.

Isolate the boiler from the electrical supply and remove the casing as described in Fig. 33. Set the flue gas analyzer to read CO2 and insert the probe into the flue analysis test point (Pos. B in Fig. 59a). Restore the electrical supply to the boiler and switch the boiler to the OFF mode. To adjust the gas valve you must first ensure that the fan speed potentiometers (trim pot) have been set correctly (Tab. 10).

Remove the 3-selector knobs, locate and press the CO button (Fig. 59). The appliance will now operate in CO mode for approximately 15-minutes.

9.GAS VALVE MAXIMUM PRESSURE SETTING (Fig. 61) Locate and gently turn the HTG trim pot until the maximum value (max fan speed) is obtained and check that it corresponds with the appropriate CO2 value (Maximum) for the respective boiler (see the data table for values). If the CO2 reading is correct, proceed to gas valve minimum setting. However, if the CO2 reading is incorrect, the maximum gas pressure must be adjusted as follows:

- Using a suitable screwdriver, very slowly turn the maximum pressure adjustment screw (Fig. 60)– clockwise to decrease, counter clockwise to increase – until the correct value is displayed on the CO2 analyzer (allow time for the analyzer to stabilize).

10.GAS VALVE MINIMUM PRESSURE SETTING

Locate and gently turn the HTG trim pot until the minimum value (min fan speed) is obtained and check that it corresponds with the appropriate CO2 value (Minimum) for the respective appliance. If the CO2 reading is correct, rotate the HTG trim pot until the correct value is obtained for the respective appliance (see fan speed Tab. 10). However, if the CO2 reading is incorrect, the minimum gas pressure must be adjusted as follows:

-Remove the sealing screw

-Using a suitable screwdriver, very slowly turn the minimum pressure adjustment screw (Fig. 60) – clockwise to increase, counter clockwise to decrease - until the correct value is displayed on the CO2 analyzer (allow time for the analyzer to stabilize).

COMPLETION

On completion of the combustion analysis check and/or any gas valve adjustment, set the HTG trim pot to the corresponding value as detailed in the fan speed table. Reattach the 3-selector knobs. Remove the test probe from the test point and reattach the sealing screws and/or cap.

DANGER: A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF ANY GAS CARRYING COMPONENTS HAVE BEEN REMOVED, REPLACED, OR DISTURBED.

11. COMBUSTION ANALYSIS TEST

A combustion analysis check can easily be carried out on the boiler via the test points located on the top of the appliance.

-Insert the flue gas analyzer probe into the flue gas test point (Pos. B in Fig. 59a).

-Operate the boiler in CO mode and compare the values with those shown in Tab. 1 (Nat. Gas) or Section 13 (LPG). If different adjust the gas valve accordingly.

12. EXTERNAL FAULTS

Before carrying out any troubleshooting or component replacement, ensure the fault is not attributable to any aspect of the installation.

INSTALLATION FAULTS

Symptom

Possible cause

No display/ignition

Check wiring/check

 

electrical supply

No hot water

Check external controls

No heating

Check external controls

Fault code

Possible cause

10

Check gas supply, check

 

flue system, check polarity,

 

check condensate

 

 

47

Page 47
Image 47
Raypak 120, 85 manual FAN SPEED rpm TABLE, Model, 5,800, 2,000, 3,700, 5,600, 1,500