BBV28581 05/2010 11
Drive ratings

Single-phase supply voltage: 100…120 V 50/60 Hz

For three Phase Output 200/240 V motors

Single-phase supply voltage: 200…240 V 50/60 Hz

For three Phase Output 200/240 V motors

Three-phase supply voltage: 200…240 V 50/60 Hz

For three Phase Output 200/240 V motors
(3)Size description
Motor Line supply (input) Drive (output) Reference
(2)
Size
(3)
Power indicated
on plate (1)
Maximum line current Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient
current for
at 100 V at 120 V 60 s 2 s
kW HP A A kVA W A A A
0.18 0.25 6 5 1 18 1.4 2.1 2.3 ATV12H018F1 1C1
0.37 0.5 11.4 9.3 1.9 29 2.4 3.6 4 ATV12H037F1 1C1
0.75 1 18.9 15.7 3.3 48 4.2 6.3 6.9 ATV12H075F1 2C1
Motor Line supply (input) Drive (output) Reference
(2)
Size
(3)
Power indicated
on plate (1)
Maximum line current Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient
current for
at 200 V at 240 V 60 s 2 s
kW HPAAkVAWA A A
0.18 0.25 3.4 2.8 1.2 18 1.4 2.1 2.3 ATV12H018M2 1C2
0.37 0.5 5.9 4.9 2 27 2.4 3.6 4 ATV12H037M2 1C2
0.55 0.75 8 6.7 2.8 34 3.5 5.3 5.8 ATV12H055M2 1C2
0.75 1 10.2 8.5 3.5 44 4.2 6.3 6.9 ATV12H075M2 1C2
1.5 2 17.8 14.9 6.2 72 7.5 11.2 12.4 ATV12HU15M2 2C2
2.2 3 24 20.2 8.4 93 10 15 16.5 ATV12HU22M2 2C2
Motor Line supply (input) Drive (output) Reference
(2)
Size
(3)
Power indicated
on plate (1)
Maximum line current Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient
current for
at 200 V at 240 V 60 s 2 s
kW HPAAkVAWA A A
0.18 0.25 2 1.7 0.7 16 1.4 2.1 2.3 ATV12H018M3 1C3
0.37 0.5 3.6 3 1.2 24 2.4 3.6 4 ATV12H037M3 1C3
0.75 16.3 5.3 2.241 4.2 6.3 6.9 ATV12H075M3 1C3
1.5 2 11.1 9.3 3.9 73 7.5 11.2 12.4 ATV12HU15M3 2F3
2.2 3 14.9 12.5 5.2 85 10 15 16.5 ATV12HU22M3 2F3
34 19 15.9 6.6 94 12.2 18.3 20.1 ATV12HU30M3 3F3
45.5 23.8 19.9 8.3 128 16.7 25 27.6 ATV12HU40M3 3F3
(1)These power ratings are for a switching frequency of 4 kHz, in continuous operation. The
switching frequency is adjustable from 2 to 16kHz.
Above 4 kHz, the drive will reduce the switching frequency if an excessive temperature rise
occurs. The temperature rise is detected by a probe in the power module. Nonetheless,
derating should be applied to the nominal drive current if continuous operation above 4 kHz
is required:
• 10% derating for 8 kHz
• 20% derating for 12 kHz
• 30% derating for 16 kHz
(2)Reference description,
example: ATV12HU15M3
ATV12: Altivar 12;
H: product on heatsink;
U15: drive power rating,
see nCU parameter page 41;
M3: drive voltage rating,
see UCAL parameter page 41.
2F3
possible values 1
2
3
physical size 1
physical size 2
physical size 3
possible values F
C
Flat
Compact
1
2
3
100 V 1 phase
200 V 1 phase
200 V 3 phase
possible values