Power terminals
Arrangement of the power terminalsATV12H
Applicable wire
size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG) mm² (AWG) N·m (lb.in)
018F1
037F1
0ppM2
0ppM3
2 to 3.5
(14 to 12)
2
(14)
0.8 to 1
(7.1 to 8.9)
ATV12H 018F1, 037F1, 0ppM2, 0ppM3
ATV12H 075F1, UppM2, U15M3, U22M3
A
TV12H U30M3, U40M3
(1)The value in bold corresponds to the minimum wire gauge to permit secureness.
(2)75°C (167 °F) copper cable (minimum wire size for rated use)
(3)Recommended to maximum value.
ATV12H
Applicable
wire size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG) mm² (AWG) N·m (lb.in)
075F1
UppM2
3.5 to 5.5
(12 to 10)
5.5
(10) 1.2 to 1.4
(10.6 to 12.4)
U15M3
U22M3
2 to 5.5
(14 to 10)
2 (14) for U15M3
3.5 (12) for U22M3
ATV12H
Applicable
wire size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG) mm² (AWG) N·m (lb.in)
U30M3
U40M3 5.5 (10) 5.5 (10) 1.2 to 1.4
(10.6 to 12.4)