BBV28581 05/2010 123
Parameter index
Code Page Name Unit Possible value / Function Factory setting User
setting
CL2 88 Current limitation 2 A 0.25 to 1.5 -1.5 A
COd 43 HMI Password - OFF
On
Code disabled
Code activated OFF
COM1 42 Modbus communication status -
r0t0
rOt1
r1t0
r1t1
--
COS 57 Rated motor cos phi - 0.5 to 1-according to
drive rating
CrH1 52 AI1 current scaling parameter
of 100% mA 0 to 20 -20 mA
CrL1 52 AI1 current scaling parameter
of 0% mA 0 to 20 -4 mA
Ctd 55 Motor current threshold In 0 to 1.5 -InV
Ctt 57 Motor control type -
Std
PErF
PUMP
Standard
Performance
Pump
Std
dCF 66 Ramp divider 1 to 10 -4
dE2 65 Deceleration 2 s 0.0 to
999.9 -5 s
dEC 45
64 Deceleration s 0.0 to
999.9 - 3.0 s
dP1 42 Last detected fault 1 - see page 107 --
dP2 42 Last detected fault 2 - see page 107 --
dP3 43 Last detected fault 3 - see page 107 --
dP4 43 Last detected fault 4 - see page 107 --
drn 96 Degraded line supply operation nO
YES
No
Yes nO
EP1 42 State of drive at detected fault 1 - - - - -
EP2 43 State of drive at detected fault 2 - - - - -
EP3 43 State of drive at detected fault 3 - - - - -
EP4 43 State of drive at detected fault 4 - - - - -