66 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
Stt- Stop configuration menu
Stt M Type of stop rMP
rMP
FSt
nSt
Stop mode on disappearance of the run command and appearance of a stop command
vRamp stop
vFast stop
vFreewheel
nSt M Freewheel stop assignment nO
nO
L1L
L2L
L3L
L4L
The stop is activated when the input or the bit changes to 0. If the input returns to state 1 and the run
command is still active, the motor will only restart if Type of control tCC page 48 = 2C and 2 wire type
control tCt page 51 = LEL or PFO. If not, a new run command must be sent.
vNot assigned
vL1L: LI1 Active Low to stop
vL2L: LI2 Active Low to stop
vL3L: LI3 Active Low to stop
vL4L: LI4 Active Low to stop
FSt M Fast stop assignment nO
nO
L1L
L2L
L3L
L4L
vNot assigned
vL1L: LI1 Active Low to stop
vL2L: LI2 Active Low to stop
vL3L: LI3 Active Low to stop
vL4L: LI4 Active Low to stop
dCF
T
M Ramp divider 1 to 10 4
Visible only if Fast stop assignment FSt page 63 is not set to nO or if FSt is set to Type of stop Stt
page 66.
The ramp that is enabled (Deceleration dEC page 45 or Deceleration 2 dE2 page 65) is then divided
by this coefficient when stop requests are sent.
Value 10 corresponds to a minimum ramp time.
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
rrS M Reverse direction nO
nO
LIH
L2H
L3H
L4H
LI1 to LI4: choice of the input assigned to the reverse command
vFunction inactive
vL1h: L1 active high
vL2h: L2 active high
vL3h: L3 active high
vL4h: L4 active high
TParameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-