92 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FLt- Fault detection management menu (continued)
FLr M Catch on the fly nO
nO
YES
Used to enable a smooth restart if the run command is maintained after the following events:
Loss of line supply or disconnection
Reset of current fault or automatic restart
Freewheel stop.
The speed given by the drive resumes from the estimated speed of the motor at the time of the restart, then
follows the ramp to the reference speed.
This function requires 2-wire level control.
vFunction inactive
vFunction active
I-O-
drC-
CtL-
FUN-
FLt-
COM-