76 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
PId- PID menu (continued)
LPI
T
M PI feedback supervision threshold nO to 100% nOAn alarm can be assigned to a relay or a logic output.
Adjustment range:
vNo: Function inactive (it will not be possible to access the other function parameters)
vbetween minimum and maximum PID feedback.
Visible only if PID feedback assignment PIF page 72 is not set to nO.
tPI
T
M PI feedback supervision function time delay 0 to 600 s 0 sVisible only if PI feedback supervision threshold LPI above is not set to nO.
AP0
T
M Maximum frequency detection hysteresis 0 to HSP 0 HzVisible only if PI feedback supervision threshold LPI above is not set to nO.
MPI M PI feedback supervision YES
Fallback mode for the PI feedback supervision function.
vYES: freewheel stop
vLFF: switch to fallback speed LFF as long as the fault is present and the run command is not disabled.
Visible only if PI feedback supervision threshold LPI above is not set to nO.
LFF M Fallback speed 0 to HSP 0 Hz
Fallback speed for PID regulator feedback supervision fault.
TParameter that can be modified during operation or when stopped.