BBV28581 05/2010 75
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
PId- PID menu (continued)
rSL M PID wake up level 0 to 100% 0%
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that unintended restarts will not present any danger.
Failure to follow these instructions will result in death or serious injury.
If PID functions and Low speed operating timetLS are set at the same time, the PID regulator may try to
set a speed lower than LSP, resulting in unwanted operation consisting of start, running at LSP, stopping
and so on…
Parameter PID wake up level rSL is used to set a minimum PID error threshold to restart after a
prolonged stop at LSP.
Visible only if PID feedback assignment PIF page 72 and Low speed operating time tLS page 74 are
not set to nO.
UPP
T
M Wake-up threshold 0 to 100% 0%
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that unintended restarts will not endanger personnel or equipment in any way.
Failure to follow these instructions will result in death or serious injury.
If PID correction reverse PIC page 74 is set to nO, enables to set the PID feedback threshold beyond
which the PID regulator is reactivated (wake-up), following a stop caused by exceeding the tLS
maximum time in low speed.
If PIC is set to YES, enables to set the PID feedback threshold above which the PID regulator is
reactivated (wake-up), following a stop caused by exceeding the tLS maximum time in low speed.
Visible only if PID feedback assignment PIF page 72 and Low speed operating time tLS page 89 are
not set to nO.
SLE
T
M Sleep Threshold Offset 0 to HSP 1 Hz
Adjustable restart threshold (offset) following a stop after prolonged operation at Low speed LSP + Sleep
Offset Threshold SLE, in Hz. The motor restarts if the reference rises above (LSP + SLE) and if a run
command is still present.
Visible only if Low speed time out tLS page xx is not set to nO and if PID feedback assignment PIF
page 72 is not set to nO.
TParameter that can be modified during operation or when stopped.