96 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FLt- Fault detection management menu (continued)
SLL M Modbus fault management YES
nO
YES
Behavior of the drive in the event of a communication fault with integrated Modbus.
vFault ignored
vFreewheel stop
WARNING
LOSS OF CONTROL
If Modbus fault mgt SLL is set to n0, communication control will be inhibited. For safety reasons, inhibition of
communication fault should only be used for adjustment or special applications purpose.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
drn M Degraded line supply operation nO
CAUTION
RISK OF DAMAGE TO THE DRIVE
When Derated operation = Yes, use a line choke.
Failure to follow these instructions can result in equipment damage.
nO
YES
Lowers the tripping threshold of the USF fault to operate on a line supply down to 50% of nominal line
voltage. In this case, the performance of the drive cannot be guaranteed
vnO
vYes
rPr
T
nO
FtH
M Reset power run nOThis reset will initialize the settings located on MOn section, menu MAI-, page 41.
vnO
vReset fan time display
To change the assignment of this parameter press the “ENT” key for 2 s.
TParameter that can be modified during operation or when stopped.