74 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
PId- PID menu (continued)
AC2
T
M Acceleration 2 0.0 to 999.9 s 5.0 s
This parameter is active only when the system is starting.
Second acceleration ramp time, adjustable from 0.1 to 999.9 s
Time to accelerate from 0 to the Rated motor frequency FrS page 57. Make sure that this value is
compatible with the inertia being driven.
Visible only if PID feedback assignment PIF page 72 and PID predictive speed SFS page 73 are not
set to nO.
PIC
nO
YES
M PID correction reverse nO
This parameter will reverse the internal error value of PID system.
vNo
vYes
Visible only if PID feedback assignment PIF page 72 is not set to nO.
PAU M PID auto/manual assignment nO
nO
L1H
L2H
L3H
L4H
At state 0 of input, PID is active.
At state 1 of input, manual run is active
vNo
vL1h: LI1 active high
vL2h: LI2 active high
vL3h: LI3 active high
vL4h: LI4 active high
Visible only if PID feedback assignment PIF page 72 is not set to nO.
PIM M PID manual reference nO
nO
A11
A1U1
This parameter allows to disable the PID and to run on a standard manual system.
vNo
vTerminal
vAIV1
Visible only if PID feedback assignment PIF page 72 and PID auto/manual assignment PAU page 74
are not set to nO.
tLS
T
M Low speed operating time 0.1 to 999.9 s nO
Following operation at Low speed LSP page 89 for a defined period, a motor stop is requested
automatically. The motor restarts if the frequency reference is greater than Low speed LSP and if a run
command is still present.
Note: nO value corresponds to an unlimited period.
Visible only if PID feedback assignment PIF page 72 is not set to nO.
TParameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-