BBV28581 05/2010 91
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FLt- Fault detection management menu
rSF M Detected fault reset assignment nO
nO
L1H
L2H
L3H
L4H
Manual fault reset.
vFunction inactive
vL1h: LI1 active high
vL2h: LI2 active high
vL3h: LI3 active high
vL4h: LI4 active high
Faults are reset when the assigned input or bit changes to 1, if the cause of the fault has disappeared.
The STOP/RESET button on the display terminal performs the same function.
See also Diagnostics and Troubleshooting on page 107.
Atr- Automatic restart menu
Atr M Automatic restart nO
DANGER
UNINTENDED EQUIPMENT OPERATION
•The automatic restart can only be used on machines or installations which do not pose any danger to either
personnel or equipment.
• If the automatic restart is activated, R1 will only indicate a fault has been detected once the time-out period for
the restart sequence has expired.
• The equipment must be used in compliance with national and regional safety regulations.
Failure to follow these instructions will result in death or serious injury.
nO
YES
This function defines drive behavior upon detection of a fault.
If validated, this function allows an automatic restart of the drive when the cause of the detected fault has
disappeared and the other operating conditions permit the restart.
vFunction inactive
vAutomatic restart, after locking on a detected fault, if the cause has disappeared and the other operating
conditions permit the restart. The restart is performed by a series of automatic attempts separated by
increasingly longer waiting periods: 1 s, 5 s, 10 s, then 1 minute for the following attempts.
The drive status relay remains activated if this function is active. The speed reference and the operating
direction must be maintained.
Use 2-wire control (Type of control tCC page 48 = 2C and 2 wire type control tCt page 51 = LEL).
If the restart has not taken place once the Max. automatic restart time tAr has elapsed, the procedure
is aborted and the drive remains locked until it is turned off and then on again.
The detected faults, which permit this function, are listed on page 109:
tAr M Max. automatic restart time 5 min
5
10
30
1H
2H
3H
Ct
v5 min
v10 min
v30 min
v1 hour
v2 hours
v3 hours
vInfinite
Visible only if Automatic restart Atr is not set to nO. It can be used to limit the number of consecutive
restarts on a recurrent fault.
I-O-
drC-
CtL-
FUN-
FLt-
COM-