56 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
I_O- Input Output menu (continued)
AO1- AO1 configuration menu
AO1 M AO1 assignment nO
nO
OCr
OFr
OrP
OPS
OPF
OPE
OPr
tHr
tHd
This parameter is used to set the value of an analog output.
vNot assigned
vMotor current, between 0 and 2 In (In = rated drive current indicated on the drive nameplate)
vOutput frequency, from 0 to Max frequency tFr
vRamp output, from 0 to Max frequency tFr
vPID reference, between 0 and 100% of the PID set point - Visible only if PID feedback assignment PIF
page 72 is not set to nO
vPID feedback, between 0 and 100% of the PID feedback - Visible only if PID feedback assignment PIF
page 72 is not set to nO
vPID error, between - 5 % and + 5 % of the PID feedback - Visible only if PID feedback assignment PIF
page 72 is not set to nO
vOutput power, between 0 and 2.5 times Rated motor power nPr
vMotor thermal state, between 0 and 200% of the rated thermal state
vDrive thermal state, between 0 and 200% of the rated thermal state
AO1t M AO1 type 0A
10U
OA
4A
This parameter provides the interface between the drive internal value and an analog output signal.
vVoltage: 0-10 Vdc
vCurrent: 0-20 mA
vCurrent: 4-20 mA
I-O-
drC-
CtL-
FUN-
FLt-