BBV28581 05/2010 97
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
COM- Communication menu
Note: For following parameters, the modifications will be taken into account only at the next control power on.
Add M Modbus address OFF to 247 OFF
Modbus address is adjustable from OFF to 247. When OFF, communication is not active.
tbr M Modbus baud rate 19.2
4.8
9.6
19.2
38.4
v4.8 kbps
v9.6 kbps
v19.2 kbps
v38.4 kbps
tFO M Modbus format 8E1
8o1
8E1
8n1
8n2
v8o1
v8E1
v8N1
v8N2
ttO M Modbus time out 0.1 to 30 s 10 s
The drive detects a Modbus fault if it does not receive any Modbus request at its address within a
predefined time period (time out).
ICS- Input scanner menu (values are expressed in hexadecimal)
nMA1 M Com scanner read address parameter 1 0C81
Address of the 1st input word.
nMA2 M Com scanner read address parameter 2 219C
Address of the 2nd input word.
nMA3 M Com scanner read address parameter 3 0
Address of the 3rd input word.
nMA4 M Com scanner read address parameter 4 0
Address of the 4th input word.
OCS- Output scanner menu (values are expressed in hexadecimal)
nCA1 M Com scanner write address parameter 1 2135
Address of the 1st output word.
nCA2 M Com scanner write address parameter 2 219A
Address of the 2nd output word.
nCA3 M Com scanner write address parameter 3 0
Address of the 3rd output word.
nCA4 M Com scanner write address parameter 4 0
Address of the 4th output word.