BBV28581 05/2010 73
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn- Function menu (continued)
PId- PID menu (continued)
Pr4 M 4 preset PID assignment nO
nO
L1H
L2H
L3H
L4H
Visible only if PID feedback assignment PIF page 72 is not set to nO.
vNo
vL1h
vL2h
vL3h
vL4h
2 preset PID assignment Pr2 page 72 must be assigned before assigning 4 preset PID assignment
Pr4.
rP2
T
M 2 preset PID reference 0 to 100% 25%Visible only if PID feedback assignment PIF page 72 and 2 preset PID assignment Pr2 page 72 are
not set to nO.
rP3
T
M 3 preset PID reference 0 to 100% 50%Visible only if PID feedback assignment ?
PIF page 72 and 4 preset PID assignment Pr4 page 72 are
not set to nO.
rP4
T
M 4 preset PID reference 0 to 100% 75%Visible only if PID feedback assignment PIF page 72 and 2 preset PID assignment Pr2 and 4 preset
PID assignment Pr4 page 72 are not set to nO.
rPI
T
M Internal PID reference 0 to 100% 0%Visible only if PID feedback assignment PIF page 72 is not set to nO and if Activation internal PID
reference PII page 72 is set to YES or Reference channel 1 Fr1 page 45 is set to LCC.
PrP
T
M PID reference ramp 0 to 100% 0%Visible only if PID feedback assignment PIF page 72 is not set to nO.
rPL
T
M PID min value reference 0 to 100% 0%Visible only if PID feedback assignment PIF page 72 is not set to nO.
rPH
T
M PID max value reference 0 to 100% 100%Visible only if PID feedback assignment PIF page 72 is not set to nO
SFS M PID predictive speed 0.1 to 400 Hz nO
This parameter allows to go directly to a set speed reference.
Visible only if PID feedback assignment PIF page 72 is not set to nO.
TParameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-