18 BBV28581 05/2010
Wiring
General wiring diagram
(1) R1 relay contacts, for remote indication of the drive status.
(2) Internal + 24 V c. If an external source is used (+ 30 V c maximum), connect the 0 V of the source to the COM terminal, and do not
use the + 24V c terminal on the drive.
(3) Reference potentiometer SZ1RV1202 (2.2 kΩ) or similar (10 kΩ maximum).
(4) Optional braking module VW3A7005
(5) Optional braking resistor VW3A7ppp or other acceptable resistor. See the possible resistor values in the catalog.
Note:
Use transient voltage surge suppressors for all inductive circuits near the drive or coupled to the same circuit (relays, contactors,
solenoid valves, etc).
The ground terminal (green screw) is located on the opposite side in comparison with its position on the ATV11 (see wiring trap label).
Single-phase supply 100...120 V
Three-phase supply 200...240 V
ATV12ppppF1
Single-phase supply 200...240 V
A
TV12ppppM2
A
TV12ppppM3
Source
3-phase