62 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
CtL- Control menu
Fr1 M Reference channel 1 AI1
AI1
LCC
Mdb
AIUI
vTerminal
vRemote display
vModbus
vIntegrated display with Jog dial
This parameter is already included in "my menu" section, page 45.
LFr
T
M External reference value -400 Hz to 400 Hz -
This parameter is already included in "my menu" section, page 45.
AIU1
T
M Analog input virtual 0% to 100%
This parameter is already included in "my menu" section, page 45.
rIn M Reverse inhibition nO
l
nO
YES
Inhibition of movement in reverse direction, does not apply to direction requests sent by logic inputs.
- Reverse direction requests sent by logic inputs are taken into account.
- Reverse direction requests sent by the display are not taken into account.
- Reverse direction requests sent by the line are not taken into account.
- Any reverse speed reference originating from the PID, etc., is interpreted as a zero reference (0 Hz).
vNo
vYes
PSt M Stop key priority YES
This parameter can enable or disable the stop button located on the drive and remote display.
Disabling the stop button is effective if the active command channel is different from the drive keypad or
remote display
WARNING
LOSS OF CONTROL
You are going to disable the stop button located on the drive and remote display
Do not select nO unless exterior stopping methods exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
nO
YES
vNo: Stop inactive
vYes: Stop active
It is advised in case this function is set to YES to use the front door cover or the option display cover on
"run" and "stop" keys.
CHCF M Channel configuration SIM

SIM

SEP
Channel configuration CHCF allows the selection of:
- Not separate mode, (command and reference come from the same channel)
- Separate mode (command and reference come from different channel)
vNot separate mode
vSeparate mode
To change the assignment of this parameter press the “ENT” key for 2 s.
TParameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s