52 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
I_O- Input Output menu (continued)
AI1- AI1 configuration menu
AI1t M AI1 type 5U
5U
10U
0A
This function makes interface from the analog input signal to a drive internal value.
vVoltage: 0-5 Vdc
vVoltage: 0-10 Vdc
vCurrent: x-y mA. Range determined by the AI1 current scaling parameter of 0% CrL1 and AI1 current
scaling parameter of 100% CrH1 settings below, see page 52.
CrL1 M AI1 current scaling parameter of 0% 0 to 20 mA 4 mA
Visible only if AI1 type AI1t is set to 0A
CrH1 M AI1 current scaling parameter of 100% 0 to 20 mA 20 mA
Visible only if AI1 type AI1t is set to 0A
I_O- Input Output menu (continued)
r1 M R1 assignment FLt
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
ULA
OLA
AP1
vNot assigned
vNo error detected
vDrive run
vFrequency threshold reached
vHSP reached
vI threshold reached
vFrequency reference reached
vMotor thermal reached
vUnderload alarm
vOverload alarm
vAI1 Al. 4-20 - Visible only if AI1t is set to 0A (see above)