BBV28581 05/2010 51
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
I_O- Input Output menu (continued)
tCt M 2 wire type control trn
LEL
trn
PFO
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the 2 wire type control is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
2-wire type control parameter can only be accessed if Type of control tCC page 48 is set to 2C.
vLevel: State 0 or 1 is taken into account for run or stop.
vTransition: A change of state (transition or edge) is necessary to initiate operation, to help prevent
accidental restarts after a power supply interruption.
vPriority FW: State 0 or 1 is taken into account for run or stop, but the "forward" input takes priority over
the "reverse" input.
nPL M Logic inputs type POS
POS
nEG
EnEG
vPositive: the inputs are active (state 1) at a voltage equal to or higher than 11 V (for example +24 V
terminal). They are inactive (state 0) when the drive is disconnected or at a voltage lower than 5 V.
vNegative using internal supply: the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V or when the drive is
disconnected.
vNegative using external supply : the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V.
Note: The modification will be taken into account only at the next control power on.
See Control connection diagrams, page 25.