LXM32M

3 Basics

 

 

3.3.3Reading and writing parameters

Parameters are processed as 32 bit values. 16 bit values must also be processed as 32 bit values. Two consecutive 16 bit parameters must be read or written to process a 16 bit parameter. The first Modbus address must be specified.

If several consecutive parameters are to be processed, a single Mod- bus command with the corresponding Modbus address and the length indication is sufficient.

NOTE: This does not apply to reading and writing parameters with addresses in the range from 17408 (4400h) to 17663 (44FFh). In this range, only a single parameter can be addressed with one Modbus command.

Example Reading the parameter CTRL1_KPp "Position controller P gain" Modbus address 4614

When the parameter CTRL1_KPp with the Modbus parameter address 4614 and length 2 is read, the two parameter addresses 4614 and

4615 are read. Result:

Address

Value

 

 

4614

0000h

 

 

4615

00C8h

 

 

0198441113843, V1.01, 01.2012

Modbus-TCP module

21

Page 21
Image 21
Schneider Electric LXM32M manual Reading and writing parameters, Address Value