5 Commissioning

LXM32M

 

 

5.7Setting I/O-Scanning

5.7.1Activating I/O scanning

I/O scanning is activated/deactivated by means of the parameter

EthMbScanner.

If you do not want to use I/O scanning, set the parameter

EthMbScanner to "Off".

Parameter name

Description

Unit

Data type

Parameter address

HMI menu

 

Minimum value

R/W

via fieldbus

HMI name

 

Factory setting

Persistent

 

 

 

Maximum value

Expert

 

 

 

 

 

 

EthMbScanner

Modbus TCP I/O scanning

-

UINT16

CANopen 3044:28h

 

0 / Off: Modbus TCP I/O scanning off

0

UINT16

Modbus 17488

 

1

UINT16

Profibus 17488

 

1 / On: Modbus TCP I/O scanning on

 

1

UINT16

CIP 168.1.40

 

 

 

I/O scanning only works if the parameter

 

R/W

 

 

EthMode is set to Modbus TCP.

 

per.

 

 

Changed settings become active immedi-

 

-

 

 

 

 

 

 

ately.

 

 

 

 

 

 

 

 

5.7.2Setting the master for I/O scanning

Entering the IP address of a master reserves I/O scanning for this master. This means that no other master on the network can perform I/O scanning.

WARNING

UNINTENDED EQUIPMENT OPERATION DUE TO UNLIMITED ACCESS

If the IP addresses are not set correctly, any network device may control the system or access by the master may be blocked.

Verify that you have set the correct master IP address.

Failure to follow these instructions can result in death, serious injury or equipment damage.

The IP address of the master for I/O scanning is set by means of the parameters EthIPmaster1 ... EthIPmaster4.

Set the IP address of the master for I/O scanning with the parame- ters EthIPmaster1 ... EthIPmaster4.

0198441113843, V1.01, 01.2012

46

Modbus-TCP module

Page 46