3 Basics

LXM32M

 

 

3.3.4I/O scanning to "Drive Profile Lexium"

I/O scanning is used for cyclic interchange of data between master and slave.

I/O scanning must be configured on the master. The master can use 2 different approaches for of I/O scanning:

"Function Code" 23 (17h), Read-Write Mulitple Registers

"Function Code" 3 (03h), Read Multiple Registers and "Function Code" 16 (10h), Write Multiple Registers

NOTE: The read value is 0 until the first write command is execu- ted.

Settings The following setting must be made on the master before you can use

I/O scanning:

The "Unit Identifier" is 255.

The Modbus parameter address is 0.

The data length is 13.

In addition, you can use up to 3 mappable parameters. If these parameters are used, the data length changes to 15, 17 or 19.

The Modbus addresses for I/O scanning do not differ from the addresses for normal Modbus access.

Output - Input Output and input refer to the direction of data transmission from the perspective of the master.

Output: Commands from the master to the slave

Input: Status messages from the slave to the master

0198441113843, V1.01, 01.2012

22