| LXM32M | 3 Basics | 
| 
 | 
 | 
3.4.6Examples
3.4.6.1 Example of "Function Code" 3
Reading an error memory entry. Since the Modbus addresses of the parameters of an error memory entry are contiguous (ascending order), a single Modbus request is sufficient.
Parameters _ERR_number (15362), _ERR_class (15364), _ERR_time (15366) and _ERR_qual (15368).
Modbus request Structure of the Modbus request:
| Field | Bytes | Value | Meaning | 
| 
 | 
 | 
 | 
 | 
| Function Code | 1 | 3 | Read Multiple Registers | 
| 
 | 
 | 
 | 
 | 
| Starting Address | 2 | 15362 (3C02h) | Address of the first parameter to be read | 
| 
 | 
 | 
 | 
 | 
| Quantity Of Regis- | 2 | 8 | Number of the 16 bit values to be read = 8 | 
| ters | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
Modbus response Structure of the positive Modbus response:
| Field | Bytes | Value | Meaning | 
 | 
| 
 | 
 | 
 | 
 | |
| Function Code | 1 | 3 | Read Multiple Registers | |
| 
 | 
 | 
 | 
 | |
| Byte Count | 1 | 16 | Number of bytes: 8 bytes of data | |
| 
 | 
 | 
 | 
 | |
| Registers Value | 16 | 32 bit value | _ERR_number, 15362 (error number) | |
| 
 | 
 | 32 bit value | _ERR_class, 15364 (error class) | |
| 
 | 
 | 32 bit value | _ERR_time, 15366 | (error time) | 
| 
 | 
 | 32 bit value | _ERR_qual, 15368 | (error qualifier) | 
| 
 | 
 | 
 | ||
3.4.6.2 Example of "Function Code" 16
Writing of the software limit switches. Since these parameters also have consecutive addresses, a single Modbus request is sufficient:
Parameters MON_swLimP (1544) and MON_swLimN (1546).
Modbus request Structure of the Modbus request:
| Field | Bytes | Value | Meaning | 
| 
 | 
 | 
 | 
 | 
| Function Code | 1 | 16 | Write Multiple Registers | 
| 
 | 
 | 
 | 
 | 
| Starting Address | 2 | 1544 (608h) | Address of the first parameter to be written | 
| 
 | 
 | 
 | 
 | 
| Quantity Of Regis- | 2 | 4 | Number of parameters = 4 (8 bytes of data) | 
| ters | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| Byte Count | 1 | 8 | Number of bytes: 8 bytes of data | 
| 
 | 
 | 
 | 
 | 
| Registers Value | 8 | 32 bit value | MON_swLimP, 1544 | 
| 
 | 
 | 32 bit value | MON_swLimN, 1546 | 
Modbus response Structure of the positive Modbus response:
| 01.2012 | 
 | 
 | 
 | 
 | |
| Field | Bytes | Value | Meaning | ||
| 
 | |||||
| 
 | 
 | 
 | 
 | 
 | |
| V1.01, | Function Code | 1 | 16 | Write Multiple Registers | |
| 
 | 
 | 
 | 
 | ||
| Starting Address | 2 | 1544 (608h) | Address of the parameter | ||
| 
 | |||||
| 
 | 
 | 
 | 
 | 
 | |
| 0198441113843, | Quantity Of Regis- | 2 | 4 | Number of parameters = 4 (8 bytes of data) | |
| ters | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
| 33 | 