6 Operation

LXM32M

 

 

6.2.5Operating mode Electronic Gear

Starting the operating mode The operating mode is set and started in the process data channel with the transmit data (master to slave).

Method

dmControl

Reference value RefA32

Reference value RefB32

 

Bits 0 ... 6

 

 

 

MODE+ACTION

 

 

 

 

 

 

Position synchronization without compen-

1Eh

As GEARdenom

As GEARnum

sation movement

 

 

 

Position synchronization with compensa-

3Eh

As GEARdenom

As GEARnum

tion movement

 

 

 

Velocity synchronization

5Eh

As GEARdenom

As GEARnum

Status information The word "driveStat" provides information on the operating mode.

Bit

Name

Meaning

 

 

 

13

X_ADD1

1: Reference velocity reached 1)

14

X_END

0: Operating mode started

 

 

1: Operating mode terminated

 

 

 

15

X_ERR

0: No error

 

 

1: Error

 

 

 

1) Only with method Velocity synchronization and with active velocity window.

Terminating the operating mode The operating mode is terminated when the motor is at a standstill and one of the following conditions is met:

Stop caused by "Halt" or "Quick Stop"

Stop caused by an error

0198441113843, V1.01, 01.2012