6.2.10 Operating mode Motion Sequence
Starting the operating mode The operating mode is set and started in the process data channel with the transmit data (master to slave).
| Method | dmControl | Reference value RefA32 | Reference value RefB32 | 
| 
 | Bits 0 ... 6 | 
 | 
 | 
| 
 | MODE+ACTION | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| Start sequence | 1Dh | Data set number | Value 1: Use data set | 
| 
 | 
 | 
 | number | 
| 
 | 
 | 
 | 
 | 
| Start individual data set | 3Dh | Data set number | - | 
| 
 | 
 | 
 | 
 | 
Status information The word "driveStat" provides information on the operating mode.
| Bit | Name | Meaning | 
| 
 | 
 | 
 | 
| 13 | X_ADD1 | 1: End of a sequence | 
| 
 | 
 | 
 | 
| 14 | X_END | 0: Operating mode started | 
| 
 | 
 | 1: Operating mode terminated | 
| 
 | 
 | 
 | 
| 15 | X_ERR | 0: No error | 
| 
 | 
 | 1: Error | 
| 
 | 
 | 
 | 
Terminating the operating mode The operating mode is terminated when the motor is at a standstill and one of the following conditions is met:
•Individual data set terminated
•Individual data set of a sequence terminated (waiting for transition condition to be fulfilled)
•Sequence terminated
•Stop caused by "Halt" or "Quick Stop"
•Stop caused by an error