0198441113843, V1.01, 01.2012

LXM32M

3 Basics

 

 

PV The double word "PV" contains the parameter value.

In the case of a read request, the value in the transmit data has no significance. The receive data contains the parameter value.

In the case of a write request, the transmit data contains the value to be written to the parameter. The receive data contains the parameter value.

If a read request or a write request were not successful, the double word "PV" contains the error number of the error.

Example: Reading a parameter In the example, the program number of the product is read from the parameter _prgNoDEV. The parameter _prgNoDEV has the parame- ter address 258 (01h 02h).

The parameter value read has the decimal value 91200 which corre- sponds to 01h 64h 40h.

Transmit data:

Ctrl

Subindex

Index

PV

 

 

 

 

12h

00h

01h 02h

00h 00h 00h 00h

 

 

 

 

Receive data:

Ctrl

Subindex

Index

PV

 

 

 

 

22h

00 h

01h 02h

00h 01h 64h 40h

 

 

 

 

Example: Writing of an invalid In this example, the value of a non-existent parameter is to be parameter changed. The parameter has the parameter address 101 (00h 65h).

The value of the parameters is to be changed to 222 (DEh).

Before the slave can accept a new request, the value 02h must first be transmitted in byte "Ctrl".

Since the slave cannot address the parameter, a synchronous error message is transmitted with the receive data. Byte "Ctrl" is set to 72h. Double word "PV" is set to the error number (error number 1101h: Parameter does not exist).

Transmit data:

Ctrl

Subindex

Index

PV

 

 

 

 

32h

00h

00h 65h

00h 00h 00h DEh

 

 

 

 

Receive data:

Ctrl

Subindex

Index

PV

 

 

 

 

72h

00h

00h 65h

00h 00h 11h 01h

 

 

 

 

See the product manual for information on the error numbers.