3 Basics

 

 

3.3Modbus TCP communication

3.3.1Connection management

Establishing of a connection The Modbus TCP server allows for TCP connections via the default port 502. A client can establish a new connection via this port. If the client is to exchange data with a remote server, a new client connec- tion via remote port 502 must be established.

Modbus data transfer A Modbus request is sent via a suitable, open connection. This TCP connection is found using the IP address of the remote device. The connection remains open for all Modbus communication. Up to 8 simultaneous connections are possible.

As described in the next chapter, a Modbus client can initialize several Modbus transactions without having to wait for the previous transac- tion to be finished.

Closing a connection After the Modbus communication between the client and a server is finished, the client causes the connection used to be closed.

The server does not close the connection under normal circumstan- ces.

However, when errors occur and in special cases, the server closes the connection, for example:

Communication errors

Communication inactivity

Maximum number of connections reached

The product can manage up to 8 TCP connections. If an attempt is made to establish a further connection beyond this maximum, the old- est unused connection is closed. If it is impossible to close the oldest unused connection, the new connection is refused.

0198441113843, V1.01, 01.2012