5 Commissioning

 

 

5.7.4Setting communication monitoring for I/O scanning

WARNING

LOSS OF CONTROL

The product is unable to detect an interruption of the network link if connection monitoring is not active.

Verify that connection monitoring is on.

The shorter the time for monitoring, the faster the detection of the interruption.

Failure to follow these instructions can result in death, serious injury or equipment damage.

Communication monitoring for I/O scanning is set by means of the parameter EthMbScanTimeout.

Set communication monitoring for I/O scanning with the parameter

EthMbScanTimeout.

Parameter name

Description

Unit

Data type

Parameter address

HMI menu

 

Minimum value

R/W

via fieldbus

HMI name

 

Factory setting

Persistent

 

 

 

Maximum value

Expert

 

 

 

 

 

 

EthMbScanTimeou

Modbus TCP I/O scanning timeout

s

UINT16

CANopen 3044:2Dh

t

Communication monitoring timeout for Mod-

0.0

UINT16

Modbus 17498

 

bus TCP.

2.0

UINT16

Profibus 17498

 

60.0

UINT16

CIP 168.1.45

 

Value 0: Timeout monitoring disabled

 

 

R/W

 

 

 

 

 

 

In increments of 0.1 s.

 

per.

 

 

Changed settings become active immedi-

 

-

 

 

 

 

 

 

ately.

 

 

 

 

 

 

 

 

5.8Setting the web server

The web server is activated or deactivated by means of the parameter

EthWebserver.

If you do not want to use the web server, set the parameter

EthWebserver to "Off".

See chapter "6.3.1 Web server" for additional information on the web server.

 

Parameter name

Description

Unit

Data type

Parameter address

 

HMI menu

 

Minimum value

R/W

via fieldbus

 

HMI name

 

Factory setting

Persistent

 

 

 

 

Maximum value

Expert

 

 

 

 

 

 

 

01.2012

EthWebserver

Ethernet webserver

-

UINT16

CANopen 3044:6h

 

1 / On: Ethernet webserver on

0

UINT16

Modbus 17420

 

1

UINT16

CIP 168.1.6

 

 

0 / Off: Ethernet webserver off

1

UINT16

Profibus 17420

 

 

 

V1.01,

 

Changed settings become active the next

 

R/W

 

 

time the product is switched on.

 

per.

 

 

 

 

 

0198441113843,

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

Modbus-TCP module