LXM32M

6 Operation

 

 

6.2.2Starting and changing an operating mode

Bits 0 ... 7 in the word "dmControl" are used to set the operating mode.

 

 

 

 

 

 

dmControl

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

14

 

13

12

11

 

10

9

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CU

CH

 

SH

-

FR

 

QS

EN

DS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

6

 

5

4

3

 

2

1

0

 

 

MT

ACTION

ACTION

MODE

MODE

 

MODE

MODE

MODE

 

 

 

 

 

 

 

 

Figure 10: Structure dmControl bits 0 ... 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

Name

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 ... 4

 

MODE

Operating mode

 

 

 

 

 

 

 

 

 

 

Value 01h: Profile Position

 

 

 

 

 

 

 

 

Value 03h: Profile Velocity

 

 

 

 

 

 

 

 

Value 04h: Profile Torque

 

 

 

 

 

 

 

 

Value 06h: Homing

 

 

 

 

 

 

 

 

Value 1Fh: Jog

 

 

 

 

 

 

 

 

 

 

Value 1Eh: Electronic Gear

 

 

 

 

 

 

 

Value 1Dh: Motion Sequence

 

 

 

 

 

 

 

 

 

 

5 ... 6

 

ACTION

Operating mode-dependent

 

 

 

 

 

 

 

 

 

 

 

7

 

MT

 

Handshake via Mode Toggle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The operating modes can be changed during operation. For this pur- pose, the current process must be completed or explicitly canceled. The motor must be at a standstill.

The master must enter the following values to activate an operating mode or to change reference values:

Reference values, depending on desired operating mode

Operating mode in "dmControl", bits 0 ... 4 (MODE).

Action for this operating mode in bit 5 and bit 6 (ACTION)

Toggle bit 7 (MT)

The following chapters describe the possible operating modes, func- tions and the corresponding reference values.

0198441113843, V1.01, 01.2012