Command Descriptions, Continued

“events” Command

“dn” Command

5.After you have selected the “hub_rom.mot” file and click on “OK,” HyperTerm will begin transmitting records to the Hub. The Hub will respond by periodically displaying addresses as the file downloads.

6.After approximately 5 minutes, the download will be complete. The hub will display messages indicating that the download has com- pleted, and it is erasing and programming the FLASH memory.

7.Finally, the Hub will reset, and display a new login prompt.

This command controls logging of hub software events. Software events mark the progress of the Hub software in some detail so board problems may be more easily analyzed. The events off command will stop the logging of event messages. The list command, as described above, is used to view the software events in the event buffer.

This command may be used to override default values for several pa- rameters related to the HDLC protocol used by DataNET. Specific forms of the command are:

dn setuptime

Displays the current “setup time” value,

 

in microseconds. This is the time that the

 

hub will transmit a “preamble” pattern on

 

a DataNET link before starting the actual

 

data frame. The preamble allows time for

 

the receiver circuitry at the far end of the

 

link to adjust to the incoming signal’s

 

amplitude, phase, and frequency. The

 

default setup time is 3500 microseconds.

dn setuptime time

Sets the HDLC setup time to the value

 

given, in microseconds. The new setup

 

time value is saved in non-volatile mem-

 

ory.

2000585-001

Command Summary 75

Page 83
Image 83