Site Wiring Requirements

Description

Wiring of Power to DataNET HUB

CE Installations

NEC Div 1, Div 2 or Non Rated Areas

Cenelec Zone 1 or Zone 2 Rated Areas

Non Rated Areas or Rack Mounting

How you wire to the DNH is dependent upon the site requirements:

CE (Conformite Europeene) Certified Areas

NEC Division 2 or Non-Hazardous Areas

Cenelec Zone 1 or Zone 2 Areas

Rack Mounting Non-Hazardous Area

The installation should have a power disconnect external to HUB enclo- sure.

No voltage dependent selections need to be made on the HUB power supply, as it has a universal input.

See Page 23, CE Installations.

Use Metal Conduit wiring method.

Conductor type: Power cable sized for circuit protection chosen. Use Cable Gland wiring method:

Conductor type: Power cable sized for circuit protection chosen, and must be shielded.

Use Metal Conduit wiring method.

Conductor type: Power cable sized for circuit protection chosen.

2000585-001

Installation 19

Page 27
Image 27