CE Installations

Description

This section should be used for installation sites that must conform to CE

 

(Conformite Europeene) Certification. Typically, this does not apply to

 

installations outside the EC unless the equipment was purchased with

 

the explicit requirements and expectations that it shall conform to EC

 

Electromagnetic and Radio Frequency Interference (EMI/RFI) rejection

 

specifications.

CE Installation Kit

Instructions

Available from Siemens Applied Automation CE Installation Kit P/N 2020264-001. This kit has all the parts for all the installations referenced in this section.

The following information pertains to CE Installation of General Purpose, Zone 1 and Division 2 Equipment. For Zone 1 Installations, all cabling is terminated in the DNH Zone 1 Enclosure.

Installation with Metallic

The preferred method is to route the field wiring in metallic conduit. If

Conduit

metallic conduit is used, unshielded power and signal wires can be used.

 

The power and signal wires (DataNET or Ethernet) must be routed in

 

separate conduit.

 

Using flexible conduit and/or armored cable is equivalent to using “steel

 

conduit”. Flexible conduit or armored cable must have its flexible conduit

 

and/or armoring conductivity 360-degree terminated at its entry to the

 

DNH enclosure (or bulkhead).

Installation without

If conduit is not used, the following installation practices must be used to

Metallic Conduit

ensure that the CE certification remains valid:

 

1. A shielded power cord or cable must be used for the input power

 

wiring. The shield must be terminated at the DNH in a 360-degree

 

termination at the enclosure (bulkhead); use Siemens Applied Auto-

 

mation P/N 2015729-001 contained in the CE Installation Kit or an

 

equivalent part. For Zone 1 Installation use Siemens Applied Auto-

 

mation P/N 1311001-014 Installation Kit.

 

2. The DataNET copper cables shields must be terminated in a 360-

 

degree termination at the enclosure (or bulkhead; use Siemens Ap-

 

plied Automation P/N 2015729-001 contained in the CE Installation

 

Kit or an equivalent part). For Zone 1 Installation, use Siemens Ap-

 

plied Automation P/N 13111001-014 Installation Kit.

2000585-001

Installation 23

Page 31
Image 31
Siemens DataNET Hub (DNH) user manual CE Installations, CE Installation Kit Instructions