CE Installations, Continued

3.A split ferrite filter must be clamped to DataNET copper wire and fixed immediately to the outside of the DNH; use Siemens Applied Automation part number 1173000-013 ferrite contained in the CE In- stallation Kit. This is required to meet the Conducted Immunity re- quirement for CE/EMC Heavy Industrial. All other CE/EMC Heavy Industrial requirements are met without the use of a ferrite clamp.

4.Shielded Ethernet cable must be used for all Ethernet connections, in and outside the GC, and coupled through the enclosure using a shielded RJ-45 coupler; use Siemens Applied Automation part num- ber 1183200-003 contained in the CE Installation Kit. A mounting plate (Siemens Applied Automation part number 2020261-001) is also available to accomplish this. If needed for Zone 1 installation, Siemens Applied Automation part numbers 2017984-001 and 2017985-001 are available to maintain purge. If a PG gland is used to make the 360-degree termination of the Ethernet shield at the en- closure, the Installation Kit and other parts are not required.

24 Installation

2000585-001

Page 32
Image 32
Siemens DataNET Hub (DNH) user manual CE Installations