GAS PRESSURES (CONT)

ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

GAS PRESSURES (CONT)

CHECKING GAS PRESSURES (CONT)

Typical manifold and supply gas pressures during:

1Standby Mode

2Pre-Purge Mode

3Heating Mode

1BLOWER OFF / GAS VALVE OFF Manifold 0.00” W.C. Supply +9.70” W.C.

Manifold

 

Supply

Gas

 

Gas

2 BLOWER ON / GAS VALVE OFF

Manifold -6.86” W.C. Supply +9.70” W.C.

5Open the supply gas shut off valve - restore power - start a heating cycle.

6The rise in manifold pressure and corresponding drop in supply gas pressure confirms the water heater’s gas valve is opening and gas is flowing to the burner.

7Record the supply and manifold gas pressures with the water heater firing.

8Supply gas pressure should not drop below minimum given in Table 2 below.

9Manifold gas pressure should be within the range shown in Table 2 below.

10Look through the burner view port (page 11) burner flame should be blue.

11Shut off power and gas supply - disconnect manometers - close test port needle valves.

12Restore power and gas supply. Check for gas

3 BLOWER ON / GAS VALVE ON

Manifold +0.05” W.C. Supply +7.04” W.C.

Manifold

Gas

Supply

Gas

Manifold Gas

Supply Gas

Service Notes - Gas Pressure Adjustment

Manifold gas pressure is factory set and should not be adjusted in the field. If manifold gas pressure differs greatly from the pressures in Table 2 consider the calibration of the manometer being used - try a different manometer. Call the technical support phone number on the water heater label for further assistance if pressures are considerably different.

Table 2 - Gas Pressures

FUEL TYPE

MINIMUM SUPPLY

MAXIMUM SUPPLY

MANIFOLD

Natural Gas

3.5” W.C. (0.87 kPa)

14.0” W.C. (3.48 kPa)

0.00” to +0.05” W.C.

(0.00 to +0.012 kPa)

 

 

 

 

 

 

 

Propane Gas

8.0” W.C. (1.99 kPa)

14.0” W.C. (3.48 kPa)

0.00” to +0.05” W.C.

(0.00 to +0.012 kPa)

 

 

 

 

 

 

 

†. Minimum supply gas pressures must be maintained under both load and no load conditions.

Technical Literature Department

17 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 