ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

SEQUENCE OF OPERATION

Call for heat initiated

Air Pressure Switch Test Is Performed Blower Prover Switch is verified open

Blocked Intake and Blocked Exhaust Switches are verified closed

YES

Blower Motor is energized

Pre-purge State

 

 

Blower Prover Switch is verified closed

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Igniter is energized for warm up period

 

 

 

 

 

 

 

 

 

(approx 17 seconds)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control System (CCB) Verifies Igniter

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

Current at 2.0 AC Amps Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve Is Energized

 

 

 

 

 

 

 

 

 

 

 

Gas Flows To Burner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control System (CCB) Verifies Flame

 

 

 

 

 

Sensing Current at 1.0µA DC Micro Amps Minimum

 

 

 

 

 

 

 

 

Control System Declares

 

 

 

Fault Condition - Locks Out

 

 

 

One of the following

 

 

 

Fault Messages Displayed:

NO

 

 

 

 

“Blower Prover Failure”

 

 

 

 

 

 

“Blocked Inlet”

 

 

 

“Blocked Exhaust Vent”

 

 

 

 

 

 

 

 

 

 

 

Control System Declares

 

 

 

Fault Condition - Locks Out

 

 

 

“Blower Prover Open”

 

 

 

Fault Message Displayed

 

 

 

 

Control System Declares

Fault Condition - Locks Out

“Low Igniter Current”

Fault Message Displayed

YES

Water Is Heated To

Operating Set Point

Gas Valve Is

De-energized

Post-Purge State

30 Sec Approx

Control System Goes Into

Standby State/Mode

NO

Gas Valve Is

De-energized

Inter-Purge State

30 Sec Approx

Retries Up To

3 Times

Control System Declares Fault Condition - Locks Out

“Ignition Failure”

Fault Message Displayed

Technical Literature Department

40 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 

Page 41
Image 41
State Industries GP650HTPDT, SHE50-100PE, SHE50-100NE manual Sequence of Operation, Yes