ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

FAULT MESSAGES (CONT)

DISPLAYED MESSAGE

CHECK/REPAIR

CONDITION/INDICATES

 

 

 

“Ignition Failure”

• Visually check for burner flame through the view

 

port on the top of the water heater (see illustra-

The control system has detected less than 1.0 µA

tions on page 11) during the Ignition Verification

operating state (Table 5 - page 31) - the Gas

(DC micro amps) through the flame sensor during

Valve icon will appear on UIM display during this

the Ignition Verification operating state on three

operating state.

consecutive trials for ignition.

• Ensure the gas supply shut off valve is open.

 

 

• Ensure there is adequate air for combustion &

 

ventilation. See air requirements in the Instruc-

 

tion Manual that came with the water heater.

 

• Ensure the burner is grounded - see electrical

 

requirements and service notes on page 8.

 

• Ensure flame sensor wiring is plugged in

 

securely at the CCB’s J4 male spade connector

 

(page 35) and at the flame sensor wiring termi-

 

nal (page 24).

Rough Starting - Rough Operation Note:

• Check all wiring between the flame sensor and

the CCB J4 connection. Repair/replace anything

 

If the water heater is experiencing rough operation

worn or damaged as necessary.

• Remove and clean the flame sensor (page 24)

or rough starting review the Service Notes - Blower

Flange & Blower Adapter Gaskets on page 13.

with fine steel wool - check for signs of exces-

 

sive wear, bent, damage, cracks in the insulator

Call the technical support phone number shown on

- replace flame sensor if worn or damaged.

the water heater labeling for further assistance if the

• Check for flame sensing current during the Igni-

problem has not been corrected after performing the

tion Verification operating state - Gas Valve icon

procedures outlined here.

will appear on UIM display (Table 5 - page 31).

 

Flame sensing current test procedure is illus-

 

trated and explained on page 24.

 

If flame sensing current measured is well above

 

the 1.0 µA (DC micro amps) minimum during

 

this test and the control system continues to

 

declare the Ignition Failure fault condition after

 

three trials - call the technical support phone

 

number shown on the water heater labeling for

 

further assistance.

 

If the flame sensing current measured is not

 

established or is below 1.0 µA - continue to the

 

next check/repair procedure.

 

 

Technical Literature Department

50 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 

Page 51
Image 51
State Industries SHE50-100PE, SHE50-100NE, GP650HTPDT manual Ignition Failure, Rough Starting Rough Operation Note