AIR PRESSURE SWITCHES (CONT)

ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

AIR PRESSURE SWITCHES (CONT)

The water heater covered in this Service Manual is factory equipped with three air pressure switches. These switches are used to provide verification or prove electrically that the blower is running and that the vent and intake air pipes are not blocked or restricted. The switches are located on the top of the water heater as shown in the illustration below.

BLOWER PROVER SWITCH

normally open contacts - close on a rise in pressure

BLOCKED INTAKE SWITCH

normally closed contacts - open on a fall in pressure

BLOCKED EXHAUST SWITCH

normally closed contacts - open on a rise in pressure

All switches have SPST(single pole single throw) contacts.

TOP VIEW

FRONT

These switches monitor air pressure through plastic sensing tubes from three different sensing ports on the water heater. The Blower Prover switch monitors pressure from the blower’s outlet flange. The Blocked Intake switch monitors pressure from the blower’s intake air connection fitting. The Blocked Exhaust switch monitors pressure from the exhaust/vent connection elbow on the bottom of the water heater. See the images below.

Blower Prover Switch

Blocked Intake Switch

Blocked Exhaust Switch

Blocked Exhaust Switch Sensing Port

Technical Literature Department

19 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 