2.2.3Installing the Netra CP3250 Blade Server in an ATCA Shelf
If you install the Sun Netra CP3250 blade server with an ARTM, the ARTM must be installed first.
Note – Slots 1 through 6 and 9 through 14 are available for Sun Netra CP3250 blade servers. Slots 7 and 8 are reserved for the switch card.
2.2.3.1Installing an Advanced Rear Transition Module (ARTM)
A compatible ARTM must be used with the Sun Netra CP3250 blade server for rear I/O access. The ARTM enables access to the network, a boot device, and a console terminal. You can use one of the Netra CP32x0 ARTMs or you can design your own
1.Verify that you have taken the necessary antistatic precautions. See Section 2.1.1, “Equipment and Operator Safety” on page
2.From the rear of the system, choose the corresponding slot for the ARTM.
The rear transition module must be installed, inline, behind a compatible Netra blade server.
For example, if the Sun Netra CP3250 blade server will be installed in slot 3, the corresponding rear transition module must be installed at the back of the system in slot 3 (FIGURE
Note – Slots 1 through 6 and 9 through 14 are available for Sun Netra CP3250 blade servers. Slots 7 and 8 are reserved for the switch card.